Galvanized mild steel is the standard and most common material used in fabricating ductwork because the zinc coating of this metal prevents rusting and avoids cost of painting. For insulation purposes, metal ducts are typically lined with faced fibreglass blankets (duct liner) or wrapped externally with fiberglass blankets (duct wrap). When necessary, a double walled duct is used. This will usually have an inner perforated liner, then a 1–2″ (2.5-5 cm) layer of fiberglass insulation contained inside an outer solid pipe.

Rectangular ductwork commonly is fabricated to suit by specialized metal shops. For ease of handling, it o any length to suit, but the most common stock sizes range evenly from 4″ to 24″ (10-60 cm) with 6″-12″ (15-30 cm) being most commonly used. Stock pipe is usually sold in 10′ (300 cm) joints. There are also 5′ (150 cm) joints of the non-spiral type pipe available, which is commonly used in residential applications

FOR SELECTION OF FLANGE CLASS & DUCT GAUGES WITHIN 1200 MM SPACING
Duct Pressure in inchesDuct Pressure in inches / (Pascals)
Dimension1″(250)2″(500)3″(750)4″(1000)6″(1500)10″(2500)
(In mm)Reinforcement Class – Duct Gauge
150-250 *126 G26 G26 G26 G26 G24 G
251-30026 G26 G26 G26 G24 G24 G
301-35026 G26 G26 G26 G24 G22 G
351-40026 G26 G26 G26 G24 G22 G
401-45026 G26 G26 G26 G24 G20 G
451-50026 G26 G24 G24 G24 G20 G
501-55026 G26 G24 G24 G24 G20 G
551-60026 G26 G24 G24 G24 G20 G
601-65026 G26 G24 G24 G24 G20 G
651-70026 G26 G24 G24 G22 G18 G
701-750*226 G26 G24 G24 G22 G18 G
751-90026 G24 G22 G22 G20 G18 G
901-100026 G24 G22 G20 G18 G16 G
1001-120024 G22 G20 G18 G18 G
1201-130024 G20 G18 G18 G16 G 
1301-150024 G18 G18 G16 G  
1501-180022 G18 G16 G   
1801-210020 G18 G    
2101-240018 G18 G    
2401-270018 G    

SMACNA – Sheet Metal and Air conditioning Contractor’s National Association Inc – “HVAC Duct Construction Standards- Metal & Flexible” -1995, U. S.A.

READING GUIDE – For Duct sizes between, say, 701 mm and 750 mm, when the pressure class is 1″ w. g. static, we require TDC Flange and duct gauge of 26. For the same range but with static pressure at 4″ w. g. TDC Flange with duct gauge of 24 should be used.